Abstract
In this paper, we present the results of a new stochastic analysis of the leakage current on contaminated insulators under salt fog conditions. The stochastic analysis of the leakage current was conducted using a Hilbert transform and the level crossing rate. The Hilbert transform is used for the leakage current envelope, while the level crossing rate is used to convert the upper envelope into a cdf. Using a new defined weighting factor, the resulting cdfs show a probability that the stages until flashover can be discriminated from each other. Therefore, the proposed method is effective for flashover prediction and for monitoring the contamination conditions of outdoor insulators.
| Original language | English |
|---|---|
| Pages (from-to) | 2693-2696 |
| Number of pages | 4 |
| Journal | Japanese Journal of Applied Physics, Part 1: Regular Papers and Short Notes and Review Papers |
| Volume | 43 |
| Issue number | 5 A |
| DOIs | |
| State | Published - May 2004 |
Keywords
- Flashover prediction
- Hilbert transform
- Insulators
- Leakage current
- Level crossing rate
- Stochastic analysis