A study on characteristics of surface discharge with interface condition

Jin Wook Choe, Woong Yup Lee, Seok Hyun Nam, Jin Gyu Kim

Research output: Contribution to journalArticlepeer-review

1 Scopus citations

Abstract

As the competition in the electrical power cable market becomes more intense, not only the quality and the price, but also the ease assembly are becoming important. The failure in the joint and termination were caused by surface discharge along the interface of cable insulation and rubber sleeve for electric field grading. The factors affecting the surface discharge are contamination, interfacial pressure, surface roughness and lubricant. In this paper, the difference of surface roughness was investigated based on the grain size of sandpaper to simplify the cable preparation process. In addition, the influence of the factors was evaluated by the surface discharge test according to the surface roughness, the interface pressure, and the type of the lubricant.

Original languageEnglish
Pages (from-to)1355-1359
Number of pages5
JournalTransactions of the Korean Institute of Electrical Engineers
Volume68
Issue number11
DOIs
StatePublished - 2019

Keywords

  • Interfacial pressure
  • Lubricant
  • Roughness
  • Surface discharge

Fingerprint