Abstract
For the digital control of systems such as grid-connected inverters, measuring inverter output currents accurately is essential. However, current measurement offsets are inevitably generated by current measurement paths and cause DC current components in real inverter output currents. Real inverter output currents with DC components cause the DC-link capacitor voltage to oscillate at the frequency of a utility voltage. For these reasons, current measurement offsets deteriorate the overall system performance. A compensation strategy to eliminate the effect of current measurement offsets in grid-connected inverters is proposed in this study. The validity of the proposed compensation strategy is verified through simulations and experiments. Results show that the proposed compensation strategy improves the performance of grid-connected inverters.
Original language | English |
---|---|
Pages (from-to) | 383-391 |
Number of pages | 9 |
Journal | Journal of Power Electronics |
Volume | 14 |
Issue number | 2 |
DOIs | |
State | Published - 2014 |
Keywords
- Current control
- Current offset
- DC component
- DC current injection
- Grid-connected inverter
- Power quality